{"company_name":"SafeGuard Compliance Services","inspection_type":"Fire Safety Inspection","report_number":"FSI-2026-0418","site_name":"Harbor Point Distribution Centre","site_address":"1200 Dockside Road, Portland, OR 97209","inspection_date":"October 13, 2026","inspector_name":"Daniel Okoye","inspector_title":"Certified Fire Inspector","client_name":"Harbor Point Logistics LLC","conditions":"Dry, 14 °C, site fully operational","site_contact":"Lisa Moreno","site_contact_title":"Facility Manager","result_summary":"The building is safe to operate. Four items need follow-up, including one overdue extinguisher service.","areas":[{"area_code":"A","area_name":"Exits and Escape Routes","items":[{"no":"1.1","item":"Emergency exits unobstructed and unlocked","pass":"X","action":"","fail":"","comment":"All 8 exits clear"},{"no":"1.2","item":"Exit signs illuminated","pass":"","action":"X","fail":"","comment":"Sign above dock door 4 is dim"},{"no":"1.3","item":"Emergency lighting operational","pass":"X","action":"","fail":"","comment":"Tested, all units lit"},{"no":"1.4","item":"Escape route plans displayed","pass":"X","action":"","fail":"","comment":"Plans current and visible"}]},{"area_code":"B","area_name":"Fire Detection and Alarms","items":[{"no":"2.1","item":"Smoke detectors tested","pass":"X","action":"","fail":"","comment":"64 of 64 responded"},{"no":"2.2","item":"Manual call points accessible","pass":"X","action":"","fail":"","comment":""},{"no":"2.3","item":"Alarm panel free of faults","pass":"X","action":"","fail":"","comment":"No active faults"},{"no":"2.4","item":"Sprinkler valves open and sealed","pass":"X","action":"","fail":"","comment":"Zones A to D checked"}]},{"area_code":"C","area_name":"Extinguishers and Equipment","items":[{"no":"3.1","item":"Extinguishers in place and signed","pass":"X","action":"","fail":"","comment":"22 units checked"},{"no":"3.2","item":"Service tags within 12 months","pass":"","action":"X","fail":"","comment":"Unit E-14 service is overdue"},{"no":"3.3","item":"Fire hose reels in working order","pass":"X","action":"","fail":"","comment":"Pressure tested"},{"no":"3.4","item":"First-aid kits stocked","pass":"X","action":"","fail":"","comment":""}]},{"area_code":"D","area_name":"Storage and Housekeeping","items":[{"no":"4.1","item":"Aisles and clearances maintained","pass":"","action":"X","fail":"","comment":"Pallets within 0.5 m of sprinklers in bay C"},{"no":"4.2","item":"Flammable materials stored correctly","pass":"","action":"X","fail":"","comment":"Cabinet door left open in workshop"},{"no":"4.3","item":"Waste removed from the building","pass":"X","action":"","fail":"","comment":""}]}],"findings":[{"finding_ref":"F-01","priority":"High","finding_title":"Expired extinguisher service tag at unit E-14","finding_detail":"The extinguisher beside dock door 6 was last serviced in July 2025 and is overdue for its annual check.","recommendation":"Replace or service the unit and update the register.","owner":"Facility Manager","due_date":"Oct 27, 2026"},{"finding_ref":"F-02","priority":"Medium","finding_title":"Stock stored too close to sprinklers in bay C","finding_detail":"Pallets are stacked within 0.5 m of the sprinkler heads, which can block the spray pattern.","recommendation":"Lower the stacks and mark the 0.9 m clearance line on the floor.","owner":"Warehouse Supervisor","due_date":"Nov 3, 2026"},{"finding_ref":"F-03","priority":"Medium","finding_title":"Flammable storage cabinet left open","finding_detail":"The cabinet in the workshop was open with solvents inside while unattended.","recommendation":"Remind staff to keep the cabinet closed and add a signed checklist.","owner":"Workshop Lead","due_date":"Nov 3, 2026"},{"finding_ref":"F-04","priority":"Low","finding_title":"Dim exit sign at dock door 4","finding_detail":"The illuminated sign is noticeably dimmer than the others and may fail its next test.","recommendation":"Replace the lamp or the unit.","owner":"Maintenance Team","due_date":"Nov 17, 2026"}],"limitations":"This inspection covers visible and accessible areas on the date shown and does not replace statutory testing of fire systems. Concealed conditions, and areas that were locked or unsafe to enter, were not inspected.","result_pass":false,"result_actions":true,"result_fail":false,"items_total":"15","items_passed":"11","items_action":"4","items_failed":"0","has_findings":true}